Wire Size & Ampacity Chart (NEC 310.16)

NEC 310.16 · Ampacity · Updated 2026-07-10

"What size wire for 100 amps?" has two honest answers, and inspectors care which one applies. The chart below is NEC Table 310.16 at the 75°C column - the column that governs almost every real termination - with the small-conductor caps of 240.4(D) noted.

Copper THHN/THWN-2 in conduit, not more than three current-carrying conductors, 30°C ambient. More conductors or hotter spaces? That's derating.

Copper ampacity chart (75°C terminations)

NEC Table 310.16, 75°C column, copper - with 240.4(D) breaker caps
SizeAmpacity (75°C)Max breaker
#1420 A15 A (240.4(D))
#1225 A20 A (240.4(D))
#1035 A30 A (240.4(D))
#850 A50 A
#665 A65 A (70 A next-up)
#485 A85 A (90 A next-up)
#3100 A100 A
#2115 A115 A (125 A next-up)
#1130 A130 A
1/0150 A150 A
2/0175 A175 A
3/0200 A200 A

The 100-amp and 200-amp answers

  • 100 A sub-panel or feeder: #3 copper or #1 aluminum at 75°C.
  • *100 A dwelling service*** (or the feeder carrying the whole dwelling load): #4 copper or #2 aluminum - NEC 310.12 allows 83% sizing for single-family dwelling services.
  • 200 A dwelling service: 2/0 copper or 4/0 aluminum (via 310.12). A 200 A feeder that isn't the whole-dwelling load needs 3/0 copper.
  • Common branch circuits: 15 A → #14 Cu, 20 A → #12 Cu, 30 A dryer → #10 Cu, 50 A range → #6 Cu (per 240.4(D) and 310.16).

Why the 75°C column (and when 90°C matters)

THHN is a 90°C wire, but breaker and lug terminations are listed at 75°C (110.14(C)), so the circuit's usable ampacity is capped at the 75°C column. The 90°C column still earns its keep as the starting point for derating - you take adjustment and correction factors off the 90°C number, then cap the result at 75°C. Continuous loads add one more step: conductors (and OCPD) at 125% of the continuous current per 210.19 and 215.2.

Wire size with the citations attached. Stop second-guessing the columns. Conduit Fill & Bending Calc sizes conductors through the full NEC pipeline and exports inspector-ready PDFs. Free on the App Store. Download Conduit Fill & Bending Calc on the App Store.

Frequently asked questions

What size wire do I need for a 100 amp sub-panel?

#3 copper or #1 aluminum at 75°C terminations (NEC 310.16). The #4-copper answer you'll hear applies only to whole-dwelling services and main feeders under the 83% rule of 310.12 - not to a garage or shop sub-panel fed as a normal feeder.

What size wire for a 200 amp service?

For a single-family dwelling service: 2/0 copper or 4/0 aluminum under NEC 310.12. For a 200 A feeder that doesn't carry the entire dwelling load: 3/0 copper (200 A at 75°C in 310.16).

Why is #12 wire limited to a 20 amp breaker if it's rated 25 A?

NEC 240.4(D) caps overcurrent protection for small conductors: #14 at 15 A, #12 at 20 A, #10 at 30 A, regardless of the table ampacity. The headroom above the cap is what derating eats before it costs you a breaker size.

Can I use the 90°C column for THHN?

Only as the starting number for derating calculations. The final ampacity can't exceed the 75°C column (or 60°C for some older or NM-cable terminations) because that's what the terminations are listed for - NEC 110.14(C).

Keep reading