Conduit Fill & Bending Calc - NEC fill checks + bend marks

Fill checks and bend marks, together. 16 NEC calculators plus 11 bend types with tape-ready marks - built for licensed electricians.

Download Conduit Fill & Bending Calc on the App Store

What Conduit Fill & Bending Calc does

Guides

All Conduit Fill & Bending Calc guides

Frequently asked questions

How many wires can I put in 3/4" EMT conduit?

At the NEC 40% fill limit, 3/4" EMT holds 16 #12 THHN or 10 #10 THHN conductors. But fill is only half the answer - with more than 3 current-carrying conductors you also owe ampacity derating, which usually caps a practical 3/4" pipe at nine current-carrying #12s. The app checks both in one screen.

Does the app calculate conduit bends, like QuickBend?

Yes - v1.5 added a full bending calculator with 11 bend types: offsets, rolling offsets, 3- and 4-point saddles, kicks, 90s, back-to-back and more. You get exact tape-ready marks in 1/16ths, a step-by-step "how to bend this" guide for every mark and flip, bender presets (Greenlee, Klein, IDEAL, Milwaukee, or your stamped deduct), a full-stick layout with cut mark, and a Site Protractor that reads the pipe angle when you lay the phone on it.

Which NEC year does Conduit Fill & Bending Calc support?

All four current cycles: NEC 2017, 2020, 2023, and 2026. Switch in one tap from the home screen and every calculation recalibrates to the tables published in that edition - so the math matches whichever code your AHJ enforces.

Are the calculations defendable to an inspector?

Every result cites the NEC table or section it came from - Chapter 9 Table 1 for fill, 310.16 for ampacity, 250.66 for GEC, 250.122 for EGC, 220.82 for dwelling load, 314.16(B) for box fill. The exported PDF reproduces every input plus the citation. Bring the PDF to the inspection.

What offset multiplier should I use for conduit bending?

The standard multipliers are 6.0 for 10°, 2.6 for 22.5°, 2.0 for 30°, 1.4 for 45°, and 1.2 for 60°. Multiply the offset depth by the multiplier to get the distance between bend marks. The app does this for you - including shrink - and rounds to tape-ready 1/16ths.

How deep does the NEC compliance go?

Deeper than most calculators on the App Store. Pipe Fill respects the Chapter 9 quirks most apps miss: the 53/31/40 fill rule, the 60% nipple rule for runs of 24 inches or less between enclosures, bare-conductor dimensions for grounds, and the multiconductor-cable-as-one-conductor rule. TW (60°C) and THW/THHW (75°C) are split into separate insulation types. Box Fill applies the 2020 NEC 314.16(B)(5) quarter-volume rule for additional EGC sets. Pull Tension uses the full Polywater straight-pull formula, so a vertical riser correctly reports double the tension of the same horizontal pull.

Do I have to derate THHN conductors in conduit?

When more than three current-carrying conductors share a raceway, NEC 310.15(C)(1) requires adjustment factors: 80% for 4-6 conductors, 70% for 7-9, 50% for 10-20. The Ampacity Derate calculator applies the factors, the ambient correction, and the termination cap in one pass - and cites each step.

Does it work without internet?

Yes. Every NEC table is on-device. Conduit Fill & Bending Calc runs in basements, crawlspaces, mechanical rooms, and remote job sites with no signal - and it's 11 MB, not a bloated reference suite.

What do I get with the full version?

All 16 NEC calculators, the complete bending suite with 11 bend types, every NEC year (2017 / 2020 / 2023 / 2026), unlimited project saves, inspector-ready PDF export with your license stamp, and photo attachments on calculations. Yearly is $9.99 with a 7-day free trial, Lifetime is $19.99 once, Monthly is $3.99.

How do I add my license to the PDF stamp?

Settings → License Information. Enter your name, license number, and state once; every PDF export from then on is stamped automatically.